Tia N.List

Reported by 9 outlets

CISA warns of critical unpatched flaw in Danfoss refrigeration controllers

new2.5
Why this score
Breadth
2.00 / 2.0 · 9 sources
Authority
1.80 / 2.0 · best outlet weight
Severity
1.00 / 5.0 · CVSS + content signals
Velocity
0.50 / 2.0 · updates in 48h
Pickup speed
0.08 / 0.6 · time to second source
Recency
× 0.46 temporal multiplier
Community
+ 0.00 / 1.5 · reddit signal
Score
2.5 / 10 = base × recency + community
bleepingcomputer.comncsc.gov.ieacdsglobal.comsekoia.commidnightblue.nlgbhackers.commalware.newsifynx.comcisa.gov CVE-2026-129713 desk first seen 13d ago

Desk analysis

CVE-2026-129713 is a CVSS 9.8 stack-based buffer overflow in the server of Danfoss AK-SM 8xxA controllers, used to manage commercial refrigeration, HVAC and lighting in food retail. CISA says an unauthenticated attacker can trigger the flaw, restart the server and potentially execute code with the web server's privileges. The affected family includes the 820A, 850A and 880A models, deployed worldwide in numbers CISA says are unknown. CISA published ICSA-26-328-03 on the advisory on 26 November.

The flaw sits inside a wider set of controller bugs. Midnight Blue researcher Carlo Meijer found six pre-authentication stack overflows in AK-SM800A firmware up to and including 5.3.2, five in sm_app web request handlers and one in the sm_fcgi_app session-control path, with root code execution demonstrated on 3.3.0. The researchers warned that OS-level access can survive factory reset and firmware update because the i.MX6 secure boot fuses are unused. Danfoss said on 20 November that CVE-2026-129713 would be fixed in an upcoming 5.5.x release, so removal from the internet remains the immediate control while that release is pending.

Timeline

  1. original reporting

    CISA warns of critical unpatched flaw in Danfoss refrigeration controllers

    bleepingcomputer.com · 1d ago · November 25th, 2026

    The U.S. Cybersecurity and Infrastructure Security Agency (CISA) is warning about a critical vulnerability in Danfoss AK-SM 8xxA Series controllers used by food retailers to manage commercial refrigeration, HVAC, and lighting systems. Danfoss controllers have been compromised recently in attacks at various supermarkets and food retailers across Europe where hackers remotely shut down cooling systems or raised their temperatures. The security issue is tracked as CVE-2026-129713 and received a severity score of 9.8. It is a stack-based buffer overflow in the controller’s server. CISA says an attacker can trigger the flaw without authentication, cause the server to restart, and potentially achieve remote code execution with the web server's privileges. Danfoss AK-SM 8xxA controllers are central control units for supermarket and convenience-store refrigeration. They are used to manage equipment such as refrigerated display cases and compressor racks, to log temperatures, and to alert when changes occur. Danfoss calls the product line the AK-SM 800A Series, which includes the 820A, 850A, and 880A models. Depending on the model, they can also control store lighting and HVAC. CISA notes that the controllers are deployed worldwide, but their exact number remains unclear. On November 20, Danfoss published a security advisory saying that the CVE-2026-129713 vulnerability would be addressed in the upcoming software version 5.5.x for Danfoss AK-SM 8xxA Series. The company said that the u

  2. update from ncsc.gov.ie

    Irish NCSC advisory on security incidents targeting remote refrigeration controllers

    ncsc.gov.ie · 23d ago · November 3rd, 2026

    Ireland's NCSC warned that attackers had gained unauthorised access to refrigeration controllers directly reachable over the public internet and could view or modify configurations. It listed Danfoss AK-SC and AK-SM series and Copeland and Dixell XWEB devices as affected families. Recommended actions included removing direct internet exposure, using a secured VPN for remote access, and reviewing temperature setpoints, defrost schedules, alarm settings, remote access permissions and user accounts.

  3. update from acdsglobal.com

    ACDS: Three weeks warning, Europes exposed refrigeration controllers after the French attacks

    acdsglobal.com · 21d ago · November 5th, 2026

    ACDS documented a second wave on November 1 and 2 in which more than a hundred stores across Belgium, Luxembourg, the Netherlands, Sweden, Estonia, Ireland and Portugal had controllers forced into defrost, with some units reaching 50C. Its mapping showed that three of the five largest exposed AK-SM 800A estates outside France were hit, while half of the world's visible controllers were still online three weeks after the first wave. By November 4 the exploitable remainder in attacked countries was down to about 200 addresses, almost all reachable only through their carrier.

  4. update from sekoia.com

    Sekoia: The cold chain on fire, unpatched Danfoss controllers exploited

    sekoia.com · 16d ago · November 10th, 2026

    Sekoia observed more than 2,700 Danfoss systems exposed worldwide on October 11, about 1,700 of them in France, and said attackers changed temperature settings, defrost cycles and alarm thresholds. Its honeypots logged unauthenticated read_units and xml.cgi requests from 26 unique IP addresses, password spraying with 12345, and a November 1 attempt to rename user ID 1 from 178.83.226[.]215 and 37.16.75[.]128. The report also notes that French authorities attributed the campaign on November 9 to the IRGC unit Shahid Kaveh, known behind the CyberAveng3rs persona.

  5. update from midnightblue.nl

    Midnight Blue: Multiple remote code execution vulnerabilities in Danfoss AK-SM800A

    midnightblue.nl · 15d ago · November 11th, 2026

    Carlo Meijer of Midnight Blue found six pre-authentication stack-based buffer overflows in AK-SM800A firmware up to and including 5.3.2 in under an hour of manual review. Five sat in sm_app web request handlers and one in the sm_fcgi_app session-control path, with root code execution demonstrated on 3.3.0 while the bugs remained present in 5.3.2. The authors warned that OS-level access could persist through factory reset and firmware update because the i.MX6 secure boot fuses were unused, and argued for cutting exposure instead of prioritising patches.

  6. update from gbhackers.com

    Researchers Discover 6 Zero-Day Vulnerabilities in Danfoss Refrigeration Controllers Allowing Remote Root Access

    gbhackers.com · 13d ago · November 13th, 2026

    They continued in […] The post Researchers Discover 6 Zero-Day Vulnerabilities in Danfoss Refrigeration Controllers Allowing Remote Root Access appeared first on GBHackers Security | #1 Globally Trusted Cyber Security News Platform .

  7. update from malware.news

    Unpatched Danfoss AK-SM800A Flaws Allow Takeover

    malware.news · 10d ago · November 16th, 2026

    Six unpatched vulnerabilities in the Danfoss AK-SM800A, a system manager that runs refrigeration in supermarkets and cold storage sites, could let a remote attacker take over the controller without logging in. The flaws became public on November 11, 2026, and there is still no fixed firmware version and no CVE ID for any of them. The timing raises the stakes. Germany’s Federal Office for Information Security (BSI), the Centre for Cybersecurity Belgium (CCB) and Ireland’s NCSC now tell operators to take AK-SM800A management interfaces off the internet, with a VPN as the minimum for any remote connection. BSI rates the issue criticality 3 (Orange), its level for immediate action, and the CCB confirmed the findings on November 12. What Did Researchers Find Inside the AK-SM800A Firmware? The team’s technical write-up classifies all six as stack-based buffer overflows reachable before any login.

  8. mentioned by ifynx.com

    Six unpatched pre-login flaws in Danfoss AK-SM800A supermarket fridge controllers can give an attacker root. No CVE, no fix yet, and Germany

    ifynx.com · 9d ago · November 16th, 2026

  9. mentioned by www.bleepingcomputer.com

    🤖 CISA warns of CVE-2026-129713 (CVSS 9.8) in Danfoss AK-SM 8xxA refrigeration/HVAC controllers: unauth stack buffer overflow, restart and p

    www.bleepingcomputer.com · 1d ago · November 25th, 2026

  10. mentioned by www.cisa.gov

    🤖 CISA ICSA-26-328-03: CVE-2026-129713 (CVSS 9.8) — unauthenticated stack buffer overflow in the CGI handler of Danfoss AK-SM 8xxA refrigera

    www.cisa.gov · 17h ago · November 26th, 2026